Laserfiche WebLink
� <br />CITY OF PEQUOT LAKES <br />Water/Wastewater Report <br />Apri12012 <br />Water Dept. <br />I. Facilitv Performance: <br />Average daily gallons pumped: 103,000 gallons <br />Maximum daily gallons pumped: 176,000 gallons <br />Minimum daily gallons pumped: 70,000 gallons <br />Total monthly gallons pumped: 3, 199,000 gallons <br />Average daily chlorine concentration: 0.53 mg/1 <br />Required chlorine concentration: 0.2 to 0.5 mg/1 <br />`,. *Average daily fluoride concentration: .93 mg/1 <br />*Required fluoride concentration: 0.9 mg/1 to 1.5 mg/I* <br />*The MDH is currently reviewing the pros and cons of fluoride addition and <br />is looking at lowering the required amount to a range of 0.6 mg/1 to 1.0 mg/1* <br />II. Onerations and Maintenance: <br />• The MN Department of Health Monthly Fluoridation Report was completed and <br />submitted. <br />• Completed weekly testing. <br />� Completed monthly Water plant maintenance <br />• Flushed all Fire Hydrants. <br />• Read the water meters <br />• Completed all Water service requests. <br />• Completed all Locate Requests. <br />• According to Minn. Dept. of Health well testing, well three has much cleaner raw water. <br />We are considering running well three as the main well and using well 4 as a backup. <br />This will save on chemical costs, and extend the life of the water filter and equipment. <br />• The school is going to hook up the Cities 12" main in Olsen Street. It will be a dead end <br />� hydrant the school will own and maintain. We intend to keep that gate valve in the off <br />position, unless told otherwise. If that 8" line to the hydrant fails the tower and the <br />town will be empty of water within a few minuets. <br />